SVS/12
60
994.530 G01 02
3.3.8
Filling the cable boxes
Materials required (figure 1)
a. Can of grease for the cable box:
for small cable box:
contents =
1.5
l
h
= 135
mm
for large cable box:
contents = 2.25
l
h
= 205
mm
for cable box with gland:
contents = 3.5 l
h
= 282
mm
b. Hand pump
c. Filling device with filling tube and valve
d. Filling hose with hose clip, shut-off ring and connector nipple
Procedure
1. Heat the can to a temperature not exceeding 100 °C,
while stirring. At this temperature the grease will be
perfectly fluid. When heating with a naked flame, keep it
away from joints and the filling opening of the can.
Then allow the grease to cool to a temperature of
approximately 80 °C.
2. Place the filling device on the can and push the filling tube
down to the bottom, see figure 2.
1.
2.
Summary of Contents for SVS/12
Page 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Page 134: ...SVS 12 134 994 530 G01 02...
Page 135: ...SVS 12 994 530 G01 02 135...
Page 136: ...SVS 12 136 994 530 G01 02...
Page 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Page 138: ...SVS 12 138 994 530 G01 02...