SVS/12
98
994.530 G01 02
3.
Clean the holes in which the sleeves
are mounted (figure 2).
Fit new sleeves greased with silicone grease and
then the end caps.
Use a polyamide thread for venting.
The sleeves, end caps and polyamide thread are
obtainable from Eaton.
Remove the polyamide thread.
4. Fit the protection cover.
5. Fit the fuses or switch the automatic fuses on the
secondary side back on.
Now the panel can be put into operation again (see
chapter 4.2.2).
4.2.10 Opening and closing the 600 mm high
instrument compartment
D
ANGER WARNING
If some components are still live while the
instrument compartment is open, the general
low-voltage safety regulations must be
observed.
Terminal block
Cont act pin
Sleeve
End cap
SVS-cable panel
Volt age
t ransf ormer
2.