SVS/12
994.530 G01 02
103
R
EMOVAL OF EARTHING
L
IFE HAZARD
!
When removing the earthing pins, never place
your hand between the red ring on the operating
rod and the earthing pins or the stop.
1. Using the operating rod, remove the earthing pins one
by one from the socket contacts (figure 1).
2. Remove the earthing cable clamps from the earth
busbar.
3. Secure the lower protection cover again using the key.
N
OTE
If the panel is put back into operation after the
earth has been removed, it is first necessary to
replace the high-voltage fuses (chapter 4.3.6),
after which the load-break switch can be
operated again (chapter 4.2.2).