SVS/12
994.530 G01 02
45
Fitting the straight plug connector
1. Clean the adapter and the plug and apply some
silicone grease.
2. Fit the plug on the special adapter in accordance with
the instructions of the manufacturer concerned.
3. Fasten the cable to the frame with a wooden terminal
block or with a cable clamp (figure 3).
Ensure that the bending radius of the cable is at
least that specified by the supplier.
For Eaton transformer cables, the bending radius is
15 times the external diameter of the cable.
4. Earth the cable sheath.
5. Place the grommet in the floor plate of the panel.
Cable clamp
3.