PROGRAMMING
INSTRUCTIONS
SINUS PENTA
321/452
NOTE
This function is ignored if the operating mode selected for the active motor is the
SLAVE
mode, i.e.
C011
=1 or 2 (motor 1),
C054
=1 or 2 (motor 2),
C097
=1 or 2 (motor 3).
Commands are factory-set to
MASTER
mode and the speed reference is selected as
factory setting (
C011
= 0 ;
C054
=0 ;
C097
= 0).
CAUTION
Switching from
MASTER
to
SLAVE
mode (or vice versa) is allowed only when the drive
is disabled.
C171 PID DISABLE Input
C171
Range
0
16
0
24 if ES847 or ES870 is fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1171
Function
This function is used for managing the PID regulator (see the PID CONFIGURATION
MENU).
When the terminal allocated to this function is activated, the PID regulator can be
disabled: its output and its external variable are set to zero.
More precisely, if the PID regulator is in
External Out
mode (
C294
=0), when the
PID
DISABLE
function is enabled, the PID output is set to zero and the external variable
regulated by the PID regulator (feedback) is no longer regulated by the PID regulator
itself.
In Reference mode, the
PID DISABLE
function disables the
PID regulator as described
above and
switches the reference,
thus becoming the main active reference again.
C171a Input for PID Control Selection
C171a
Range
0
16
0
24 if ES847 or ES870 is fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ENGINEERING
Address
1188
Function
This parameter pertains to the activation of the two PIDs or the 2-zone mode (see the
PID CONFIGURATION MENU).
It allows using the PID regulator outputs in different ways and allows disabling the 2-
zone mode.