PROGRAMMING
INSTRUCTIONS
SINUS PENTA
327/452
C185 STOP Mode
C185
Range
0 ÷1
0: [Deceleration Ramp] – 1:[Idling]
Default
0
0: [Deceleration Ramp]
Level
ADVANCED
Address
1185
Function
This function allows selecting whether the drive is to be deactivated with a controlled
deceleration ramp or is left idling when the
START
command is open.
C186 Fire Mode Enable Input
C186
Range
0
16
0
24 if ES847 or ES870 is
fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ENGINEERING
Address
1186
Function
This parameter allows programming a digital input to activate the Fire Mode (see the Fire Mode section).
C187 Torque Limit Source Ref. Disable Input
C187
Range
0
16
0
24 if ES847 or ES870 is
fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1187
Function
This function sets a digital input allowing disabling the external torque limit. When the
digital input set for
C187
is active, the torque limit will depend on the parameters
contained in the LIMITS MENU of the active motor.
C188a, C188b, C188c Inputs for PID MULTIREFERENCES
C188a
C188b
C188c
Range
0
16
0
24 if ES847 or ES870 is
fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1365, 1366, 1367
Function
This function allows generating up to 7 PID references that can be programmed with
parameters
P081a
to
P087a
according to the operating mode selected with
P080a
.
The 3 functions determine which is the active reference among the 7 available PID
references: the active value (
1
) or the inactive value (
0
) of each programmed input signal
determines a bit-logic value, where
MULTIREF 0
is the least significant bit (bit 0) and
MULTIREF 2
is the most significant bit (bit 2).
If one of the available functions is not programmed, the value of the relevant bit is “zero”.
Table 96: Selection of PID Multireferences.
Bit 2
Bit 1
Bit 0
Multireference selected =
MULTIRFERENCE 2
MULTIRFERENCE 1
MULTIRFERENCE 0