SINUS PENTA
PROGRAMMING
INSTRUCTIONS
294/452
NOTE
If the keypad is enabled as a command source, the
START
,
STOP
,
RESET
,
LOC/REM,
FWD/REV
functions are enabled (to disable
LOC/REM
and
FWD/REV
see parameter
P269
). The keypad is ignored for the processing of logic functions (AND/OR) of the other
command sources that are enabled at that moment.
NOTE
As the
ENABLE
command of the
hardware terminal board
is a hardware safety device
(it enables the drive) it is always active, even when none of parameters
C140, C141
or
C142
selects the terminal board (=1).
NOTE
The commands for the
External Alarm n.1, n.2, n.3
functions
are always considered for
the drive terminal board only
.
NOTE
The
LOCAL mode,
that can be enabled with the
LOC/REM
key from the keypad or with
the
LOCAL
command function from the terminal board (see
C180
), forces the keypad as
the only command source, thus ignoring the values set in parameters
C140
,
C141
,
C142
.
The following functions are therefore enabled for the hardware terminal board:
External
Alarm n.,1 n.2, n.3
,
Motor Sel. n.2
,
Motor Sel. n.3
,
SLAVE
,
Source Selection
,
LOCAL
and the
ENABLE
and
RESET
functions are always enabled for terminals
MDI2
and
MDI3
.
Table 82: Remote command inputs from serial link.
MODBUS
Address
Input
Code
User Level
Description
Range
1406
I019
BASIC
Remote, virtual terminal board
from serial link
Bit input: 0
1 for 8 bits
corresponding to MDI1
MDI8
1407
I020
BASIC
Auxiliary, virtual terminal board
from serial link
Bit input: 0
1 for 8 bits
corresponding to XMDI1
XMDI8
NOTE
I020
is enabled only if
R023
is set other than 0.
Example:
If
C140
= 3 (Fieldbus) and
C141
= 2 (Serial link), the
ENABLE
command is sent by closing terminal
MDI2
on the
terminal board and (AND) by forcing bit
MDI2
from the serial link on input
I019
(MODBUS address: 1406)
and
bit
MDI2
from Fieldbus (see the FIELDBUS CONFIGURATION MENU).
The
START
command may also be sent (OR) by forcing bit
MDI1
from serial link on input
I019
or
by forcing bit
MDI1
from Fieldbus for the relevant variable.