SINUS PENTA
PROGRAMMING
INSTRUCTIONS
270/452
C029 (C072,C115) Max. Motor Speed
C029 (Motor 1)
C072 (Motor 2)
C115 (Motor 3)
Range
0
32000
(*see
note
in
parameter
C028
)
0
32000 rpm (*see note in parameter
C028
)
Default
1500
1500 rpm
Level
BASIC
Address
1029, 1072, 1115
Function
This parameter defines the maximum speed of the connected motor. When
references forming the global reference are at their max. relative value, the global
reference equals the max. speed of the connected motor.
If
C011
(
C054
,
C097
)
= 2: Torque with speed limit
,
this parameter is used to limit
the motor rotation.
NOTE
In the
CONTROL METHOD MENU, if an external speed/torque limit source (
C147
) is selected,
the speed limit value set with this parameter is the upper limit, that can be reduced by
adjusting the external source. Also, the ramp times set in the RAMPS MENU (
P009–P025
) are
applied to this limit.
C030 (C073,C116) Flux Weakening Speed
C030 (Motor 1)
C073 (Motor 2)
C116 (Motor 3)
Range
0
200
0%
200%
Default
90
90%
Level
ENGINEERING
Address
1030, 1073, 1116
Control
FOC
Function
This parameter defines the speed value determining the motor flux weakening.
It is expressed as a percentage of the motor rated speed:
C016
(
C059
,
C102
)
C031 (C074,C117) Max. Speed Alarm
C031 (Motor 1)
C074 (Motor 2)
C117 (Motor 3)
Range
0
32000
0: (Disabled)
32000 rpm
Default
0
0: Disabled
Level
ADVANCED
Address
1031, 1074, 1117
Function
If it is not set to zero, this parameter determines the speed value to be entered for
the maximum speed alarm (
A076
).