SINUS PENTA
PROGRAMMING
INSTRUCTIONS
414/452
R116 Preset Connections (Line 4)
R116
Line 4
Range
0
20
See Table 120
Default
0
0: no active preset
Level
ENGINEERING
Address
134
Function
This parameter allows forcing one of the available connecting modes to the Data Logger
ES851 board. The parameters used for Ethernet connections and modem connections
are the ones stored in the Penta drive.
Configurations 19 and 20 support both dial in and dial out.
NOTE
After imposing any of the preset values given in Table 120, the Data Logger is forced to
Interlocked mode (see the Data Logger Measures Menu).
Table 120: Preset connections.
Value
COM
Baudrat
e[bps]
Stop
bit
Parity
Delay
[ms]
0
No active presetting
1
Ethernet enabled
2
PPP null modem
3
1(RS232
)
38400
2
no
2
4
1(RS232
)
38400
1
no
2
5
1(RS232
)
38400
2
no
20
6
1(RS232
)
38400
1
no
20
7
1(RS232
)
9600
2
no
2
8
1(RS232
)
9600
1
no
2
9
1(RS232
)
9600
2
no
20
10
1(RS232
)
9600
1
no
20
11
2(RS485
)
38400
2
no
2
12
2(RS485
)
38400
1
no
2
13
2(RS485
)
38400
2
no
20
14
2(RS485
)
38400
1
no
20
15
2(RS485
)
9600
2
no
2
16
2(RS485
)
9600
1
no
2
17
2(RS485
)
9600
2
no
20
18
2(RS485
)
9600
1
no
20
19
Dial Out analog modem
20
Dial Out GSM modem