5 .4 .
Configuring the Feedback from Encoder
In the Encoder/Frequency Input menu,
set the source for Encoder B speed
feedback: set C189 [A=NO B=FBK] (if
also encoder A or frequency input FIN A
are used, see programming options for
C189 in the Encoder/Frequency Input
section).
Set the number of pls/rev for the
encoder being used (parameter C191).
Setting the Speed
Feedback
In the Motor Control menu,
set C012 as a speed
feedback from Encoder.
Selecting the Encoder
ENCODER A
Push-Pull, single-ended 24V encoder
connected to digital inputs MDI6
and MDI7.
NOTE: In the Digital Inputs menu, do
not set any function for MDI6 and
MDI7.
ENCODER B
Encoder
acquired
via
option
board ES836 (see the Installation
Instructions
manual
for
the
Configuration of the jumper and
the dip-switches for the encoder
type and supply).
In
the
Encoder/Frequency
Input
menu, set the source for Encoder A
speed feedback: set C189 [A=FBK
B=NO]
(if
also
encoder
B
or
frequency input FIN B are used, see
the programming options for C189 in
the
Encoder/Frequency
Input
section).
Set the number of pls/rev for the
Checking the
Check to see if the encoder is properly connected.
CAUTION: the motor must start running.
In the Autotune menu, set I073=Encoder Tune and close the enabling
contact of the drive (MDI2). When autotune is over, one of the following
messages is displayed:
•W31 Encoder Ok (encoder direction matches with the motor direction of
rotation)
•A059 Encoder Fault (wrong encoder reading: check parameters in the
Encoder/Frequency Input menu and check wiring. If encoder B is used,
check the configuration of the dip-switches in the encoder board and
the configuration of the jumper selecting the encoder supply mode
.)
When performing the Autotune function, the encoder signal used as
feedback is automatically corrected (see C199).
Setting
P000 Write Enable
P001 = Eng. (Access Level)