PROGRAMMING
INSTRUCTIONS
SINUS PENTA
167/452
P237b Wake-up Level
P237b
Range
–10000
+10000
–100.00
+100.00 %
Default
0
0.00 %
Level
ENGINEERING
Address
859
Function
Level of the Feedback or Error signal allowing re-activating the PID control
(see
P237a
).
TIME
TIME
PID Output
PID Feedback
Sleep Level
Wake-Up Level
P237b
P237
RUNNING
STOP
T > P255
P000666-b
P237a = 1 [Feedback < P237b]
Figure 30: PID Sleep and Wake-up Mode when P237a is set to 1.
P238 Max. Value of Integral Term
P238
Range
0
10000
–100.00
+100.00 %
Default
10000
+100.00 %
Level
ENGINEERING
Address
838
Function
This is the max. allowable value of the integral term. It is to be considered
as an absolute value; the output value resulting from the integral term
ranges from +
P238
to
– P238.