PROGRAMMING
INSTRUCTIONS
SINUS PENTA
289/452
C043 (C086, C129) Current Limit While accelerating
C043 (Motor 1)
C086 (Motor 2)
C129 (Motor 3)
Range
0
400 (*)
0: Disabled
1.0%
Min[
Ipeak inverter/Imot, 400.0%
]
Default
150%
Level
BASIC (C043); ADVANCED (C086, C129)
Address
1043, 1086, 1129
Control
IFD
Function
This parameter defines the current limit while accelerating; it is expressed as a
percentage of the rated current of the selected motor.
(*)
The maximum allowable value depends on the drive size.
C044 (C087, C130) Current Limit at Constant Rpm
C044 (Motor 1)
C087 (Motor 2)
C130 (Motor 3)
Range
0
400 (*)
0: Disabled
1.0%
Min[[
Ipeak inverter/Imot, 400.0%]
Default
150%
Level
BASIC (C044); ADVANCED (C087, C130)
Address
1044, 1087, 1130
Control
IFD
Function
This parameter defines the current limit at constant rpm; it is expressed as a
percentage of the rated current of the selected motor.
(*)
The maximum allowable value depends on the drive size.
C045 (C088, C131) Current Limit while Decelerating
C045 (Motor 1)
C088 (Motor 2)
C131 (Motor 3)
Range
0
400 (*)
0: Disabled
1.0%
Min[
Ipeak inverter/Imot, 400.0%
]
Default
See Table 74 and Table 78
Level
BASIC (C045); ADVANCED (C088, C131)
Address
1045, 1088, 1131
Control
IFD
Function
This parameter defines the current limit while decelerating; it is expressed as a
percentage of the rated current of the selected motor.
(*)
The maximum allowable value depends on the drive size.
C046 (C089, C132) Current Limit Decrease in Flux Weakening
C046 (Motor 1)
C089 (Motor 2)
C132 (Motor 3)
Range
0
1
0: Disabled
1: Enabled
Default
0
0: Disabled
Level
ADVANCED
Address
1046, 1089, 1132
Control
IFD
Function
This parameter enables the current limit decrease function in flux weakening.
The current limit is multiplied by the ratio between the motor rated torque and
the frequency forced to the drive:
limit = current limit being used * (Fmot/ Fout).