SINUS PENTA
PROGRAMMING
INSTRUCTIONS
346/452
C218 DCB at Start Duration
C218
Range
1 ÷ 600
0.1; 60.0 sec.
Default
5
0.5 sec
Level
ADVANCED
Address
1218
Control
IFD and VTC
Function
Determines the duration of the DCB at Start function.
C219 Speed at the Beginning of DCB at Stop
C219
Range
0; 1000
0; 1000 rpm
Default
50
50rpm
Level
ADVANCED
Address
1219
Control
IFD and VTC
Function
Determines the speed at the beginning of DCB at stop while decelerating.
C220 DCB Current Level
C220
Range
0
MIN [ (Ipeak inverter/Imot)*100) ; 120]
0%
Min[Ipeak inverter/Imot,
120%]
Default
100
100%
Level
ADVANCED
Address
1220
Control
IFD and VTC
Function
Determines the level of direct current injected to brake the motor.
It is expressed as a percentage of the rated current of the controlled motor.
C221 DCB Hold
C221
Range
0 ÷ 100
0; 100%
Default
0
0%
Level
ADVANCED
Address
1221
Control
IFD
Function
Determines the level of direct current injected during the Hold function.
To activate this function, set a value other than zero in parameter
C221
.
DC level is expressed as a percentage of the rated current of the controlled
motor.
C222 (C223, C224) Ramp Braking Time for DCB
C222 (Motor 1)
C223 (Motor 2)
C224 (Motor 3)
Range
2
32000
2
32000 msec
Default
See Table 74 and Table 78
Level
ENGINEERING
Address
1222, 1223, 1224
Control
IFD and VTC
Function
This parameter represents the time required for flux weakening before DCB.