SINUS PENTA
PROGRAMMING
INSTRUCTIONS
126/452
1 7.2.
List of Parameters P115 to P121
Table 26: List of parameters P115 to P121.
Parameter
FUNCTION
User Level
Default
Values
MODBUS
Address
P115
Reference variation percent n.1
ENGINEERING
0.0%
715
P116
Reference variation percent n.2
ENGINEERING
0.0%
716
P117
Reference variation percent n.3
ENGINEERING
0.0%
717
P118
Reference variation percent n.4
ENGINEERING
0.0%
718
P119
Reference variation percent n.5
ENGINEERING
0.0%
719
P120
Reference variation percent n.6
ENGINEERING
0.0%
720
P121
Reference variation percent n.7
ENGINEERING
0.0%
721
P115 (
P121) Reference Variation Percent n.1 (
n.7)
P115 (
P121)
Range
1000
100.0%
Default
0
0.0%
Level
ENGINEERING
Address
715 (
721)
Function
These parameters define the variation percent of the current reference (
M000
for speed control,
M007
for torque control,
M018
if PID control is activated) to
be considered as a ramp reference when selecting variation percent 1 (
7).