SINUS PENTA
PROGRAMMING
INSTRUCTIONS
318/452
C164 , C165, C166 External Alarm Inputs
C164
C165
C166
Range
0
16
0
24 if ES847 or ES870 is fitted
0
Inactive
1
8
MDI1
MDI8
9
12
MPL1
MPL4
13
16
TFL1
TFL4
17
24
XMDI1
XMDI8
Default
0
Inactive
Level
ADVANCED
Address
1164, 1165, 1166
Function
When allocating one of these 3 functions to a digital input, the status of this input will
ALWAYS BE CHECKED ON THE DRIVE’S TERMINAL BOARD
.
When the command contact opens, the drive is locked due to an alarm tripped.
Parameters
C164a, C165a, C166a
allow delaying external alarms.
To restart the drive, the digital input set as an external alarm must be closed and a
Reset procedure is required.
Alarms tripped due to these 3 functions are
A083
,
A084
,
A085
respectively.
This function is factory set as disabled.
CAUTION
The terminal board for these 3 functions is the hardware terminal board of the drive. If
different command sources are enabled (see the CONTROL METHOD MENU), the
“External Alarm” signal command is obtained only for the hardware terminal board of the
drive. Therefore, in order to avoid any external alarm, the input signal for the active
terminal must be active in the terminal board.
Alarms trip when only one input signal for the terminal selected on one of the active
command sources is disabled. A trip delay can be programmed with parameters
C164a,
C165a, C166a.
C164a (C165a, C166a) External Alarm Trip Delay
C164a
C165a
C166a
Range
0
32000
0
32000 msec
Default
0
Instantaneous
Level
ADVANCED
Address
1305, 1306, 1307
Function
External alarm trip delay. To avoid untimely alarm trip, it may be necessary to set a
check time for the opening of the input set as an external alarm before the alarm
trips.