SINUS PENTA
PROGRAMMING
INSTRUCTIONS
78/452
P001 User Level
P001
Range
0÷2
0: Basic
1: Advanced
2: Engineering
Default
0
0 : Basic
Level
BASIC
Address
514
Function
The inverter programming parameters are grouped by access levels based on their
functions (more or less complex functions).
Some menus, or some parts of menus, are not displayed when a given access
level is selected.
When the BASIC access level is selected once the inverter parameterization is
correct, navigation is easier, as only frequently accessed parameters are displayed.
The User Level is stated for each parameter
.
P002 Password for Write Enable
P002
Range
00001 ÷ 32767
00001 ÷ 32767
Default
00001.
Level
ENGINEERING
Address
510
Function
Once write is enabled after entering the correct password in
P000
, you can use
parameter P002 to enter a custom password.
CAUTION
The new password allowing parameter write enable is the value entered in P002.
Note it down and keep it handy!
P003 Conditions for C Parameter Modifications
P003
Range
0 ÷ 1
0:[Stand-by only] ÷ 1:[Fluxing]
Default
1
1:[Fluxing]
Level
ADVANCED
Address
509
Function
Factory setting
allows
C
parameters
to be programmed even when the inverter is
enabled. However, the motor must be stopped. If
P003=0:
[Stand-by only]
,
C
parameters
can be changed only when the inverter is disabled.
This parameter also affects the behaviour of the digital inputs for
LOC/REM
and
motor selection: when those inputs change, they produce their effect only when C
parameters are allowed to be changed, according to the value in
P003
.
CAUTION
If
P003 = 1:[Fluxing]
when changing a C
parameter, the drive automatically
disables (stops modulating) and the motor starts idling.
NOTE
If
C020 = 0: IFD [Voltage/Frequency]
, C parameters may be set up when the Enable input
is active and the motor is stopped independently of
P003
.