PROGRAMMING
INSTRUCTIONS
SINUS PENTA
211/452
P320 Channel 1: Measure Mode
P320
Range
0
1
0: no input
1: val PT100
Default
0
0: no input
Level
ADVANCED
Address
920
Function
This parameter selects the type of analog signal available in terminals 27–28 in
ES847 expansion board.
0:
no signal is used. The P parameter relating to the analog input disappears.
1
: val PT100. The acquired signal is transformed into degrees centigrade.
See Measure
M069.
P321 Channel 1: Measure Offset
P321
Range
–30000 ÷ 30000
–300.00 ÷ 300.00
Default
0
0.0 °C
Level
ADVANCED
Address
921
Function
Value of the measure offset for channel 1: an offset can be applied to the
measure to correct possible errors.
P322 Channel 2: Measure Mode
P322
Range
0
1
0: no input
1: val PT100
Default
0
0: no input
Level
ADVANCED
Address
922
Function
This parameter selects the type of analog signal available in terminals 29–30 in
ES847 expansion board.
0:
no signal is used. The P parameter relating to the analog input disappears.
1
: val PT100. The acquired signal is transformed into degrees centigrade.
See Measure
M070.
P323 Channel 2: Measure Offset
P323
Range
–30000 ÷ 30000
–300.00 ÷ 300.00
Default
0
0.0 °C
Level
ADVANCED
Address
923
Function
Value of the measure offset for channel 2: an offset can be applied to the
measure to correct possible errors.