PROGRAMMING
INSTRUCTIONS
SINUS PENTA
139/452
20.2.2.
A
NA L OG
O
UTP UT
P
ROG RAMMING
E
X A MP LE S
This section contains a description of operating examples of the analog outputs obtained with different programming
modes.
Example 1:
Table 30: Programming AO1 (0÷ 10V).
Parameterization of AO1 Analog Output
Parameter
Value
Description
P176
0÷10V
AO1 Analog output
P177
1: Speed
Selected variable for AO1 analog output
P178
–500 rpm
Min. value of AO1 selected variable
P179
+500 rpm
Max. value of AO1 selected variable
P180
0.000 V
AO1 Analog output offset
P181
0 ms
Filter for AO1 analog output
P182
0.0 V
Min. AO1 output value with reference to
P178
P183
10.0 V
Max. AO1 output value with reference to
P179
Figure 17: Curve (voltage; speed) implemented by AO1 (Example 1).
0
1
2
3
4
5
6
7
8
9
10
-500 -400
-300 -200 -100
0
100
200
300
400
500
( rpm )
( V )
Example 2:
Table 31: Programming AO1 (ABS 0 ÷ 10V).
Parameterization of Analog Output AO1
Parameter
Value
Description
P176
ABS 0÷10V
AO1 Analog output
P177
1: Speed
Selected variable for AO1 analog output
P178
0 rpm
Min. value of AO1 selected variable
P179
+500 rpm
Max. value of AO1 selected variable
P180
0.000 V
AO1 Analog output offset
P181
0 ms
Filter for AO1 analog output
P182
0.0 V
Min. AO1 output value with reference to P178
P183
10.0 V
Max. AO1 output value with reference to P179