M026 Output Current
M026
Range
0
65535
0
6553.5 A
Note: The actual range depends on the drive size.
Active
Always active.
Address
1676
Function
Measure of the RMS of the output current.
M026a Motor Thermal Capacity
M026a
Range
0
1000
0.0
100.0%
Active
Always active.
Address
1728
Function
Heating of the connected motor.
This parameter indicates the current level of the motor heating following I2t pattern set in the
MOTOR THERMAL PROTECTION MENU. This value is expressed as a percentage of the
allowable asymptotic value.
M027 Output Voltage
M027
Range
0
65535
0
65535 V
Note: The actual range depends on the drive voltage class.
Active
Always active.
Address
1677
Function
Measure of the RMS of the output voltage.
M028 Output Power
M028
Range
0
65535
0
6553.5 kW
Note: The actual range depends on the drive size.
Active
Always active.
Address
1678
Function
Measure of the active power produced by the drive.
M028a Energy Consumption
M028a
Range
0
1000000000
0
10000000.00 kWh
Active
Always active.
Address
1723-1724 (LSWord, MSWord)
Function
Counter of the drive energy consumption.
This is a value expressed in 32 bits divided into two 16-bit words: the low part and the high
part.