SINUS PENTA
PROGRAMMING
INSTRUCTIONS
146/452
P184 AO2 Analog Output
P184
Range
0
7
0: Disabled,
1: ± 10V,
2: 0 ÷ 10V,
3: 0 ÷ 20mA,
4: 4 ÷ 20mA,
5: ABS 0 ÷ 10V,
6: ABS 0 ÷ 20mA,
7: ABS 4 ÷ 20mA.
Default
1
1: ± 10V
Level
ADVANCED
Address
784
Function
Selects the operating mode of AO2 analog output.
NOTE
Analog outputs are set as voltage outputs by default. To set them as current outputs, see
the DIP-switch configuration and follow the instructions displayed on the keypad, or refer
to the Sinus Penta’s Installation Instructions Manual.
P185 Selected Variable for AO2 Analog Output
P185
Range
0
69
See Table 29
Default
2
Reference at constant speed
Level
ADVANCED
Address
785
Function
Selects the variable to be allocated to AO2 digital output.
P186 Min. Value of AO2 Selected Variable
P186
Range
–32000
+32000
Depends on the value
selected in
P185
–320.00 %
+320.00 % of the full-scale value
See Table 29
Default
–1500
–1500 rpm
Level
ADVANCED
Address
786
Function
Minimum value of the variable selected via
P185
,
corresponding to the min.
output value of AO2 set in
P190
.
P187 Max. value of AO2 Selected Variable
P187
Range
–32000
+32000
Depends on the value
selected in
P185
–320.00 %
+320.00 % of the full-scale value
See Table 29
Default
+1500
+1500 rpm
Level
ADVANCED
Address
787
Function
Maximum value of the variable selected via
P185
,
corresponding to the max.
output value of AO2 set in
P191
.