PROGRAMMING
INSTRUCTIONS
SINUS PENTA
305/452
As shown in the figure above, the digital input status is displayed in measures
M031
,
M032
,
M033
.
Measure
M033
shows the
current
status of the 8 inputs in the local hardware terminals in the drive board.
The symbol displays the logic levels for terminals
M033
for inactive inputs; the active inputs are marked
with .
Measure
M032
shows the
current
status of the virtual terminal board obtained by processing all active
terminal boards. It includes 10 signals, with two additional signals with respect to the local hardware terminal
board:
Inputs
MDI1
~
MDI8
are obtained with the
logic
OR
of the input signals for all active terminals;
The
ENABLE
input is obtained with the logic
AND
of the input signals for terminal
MDI2
in all active
terminal boards;
The
ENABLE–S
input is obtained with the logic
AND
of the terminals selected for this function in all
active terminal boards.
Measure
M031
is similar to
M032
, but it displays the status of the terminal board obtained after delaying the input
signals of M032 using special timers.
The drive uses this terminal board to acquire digital commands.
Some functions cannot be programmed, but they are assigned to special terminals:
Table 85: Unprogrammable functions.
Function
Terminal
ENABLE
MDI2
RESET
MDI3 (can be disabled if
C154
=Yes)
Some terminals in the local hardware terminal board can also be used for different functions:
Table 86: Terminals used for other inputs.
Terminal
Description
MDI6
ECHA: channel A of
encoder A
in the terminal board
MDI7
ECHB: channel B of
encoder A
in the terminal board
MDI8
FIN: frequency input