SINUS PENTA
PROGRAMMING
INSTRUCTIONS
206/452
25.
AUXILIARY
DIGITAL
OUTPUTS
MENU
2 5.1.
Overview
This menu includes the parameters allowing allocating the control functions implemented via the digital inputs located
on I/O expansion boards. This menu can be viewed only after enabling data acquisition from the expansion boards.
2 5.2.
List of Parameters P306 to P317
Table 50: List of parameters P306 to P317.
Parameter
FUNCTION
User Level
DEFAULT
VALUES
MODBUS
Address
P306
XMDO1: Signal selection
ENGINEERING
D0: Disable
906
P307
XMDO1: Output logic level
ENGINEERING
1: True
907
P308
XMDO2: Signal selection
ENGINEERING
D0: Disable
908
P309
XMDO2: Output logic level
ENGINEERING
1: True
909
P310
XMDO3: Signal selection
ENGINEERING
D0: Disable
910
P311
XMDO3: Output logic level
ENGINEERING
1: True
911
P312
XMDO4: Signal selection
ENGINEERING
D0: Disable
912
P313
XMDO4: Output logic level
ENGINEERING
1: True
913
P314
XMDO5: Signal selection
ENGINEERING
D0: Disable
914
P315
XMDO5: Output logic level
ENGINEERING
1: True
915
P316
XMDO6: Signal selection
ENGINEERING
D0: Disable
916
P317
XMDO6: Output logic level
ENGINEERING
1: True
917
P306 XMDO1: Signal Selection
P306
Range
0
59
See Table 41
Default
0
D0: Disable
Level
ENGINEERING
Address
906
Function
Selects the digital signal used to calculate the value of
XMDO1
digital output.
It selects an analog variable used to calculate the value of
XMDO1
digital input
if one of the “analog” operating modes is selected.
Digital signals and analog variables are detailed in Table 41.
P307 XMDO1: Output Logic Level
P307
Range
0–1
0: FALSE
1: TRUE
Default
1
1: TRUE
Level
ENGINEERING
Address
907
Function
XMDO1
digital output logic function to apply a logic reversal (negation) to the
calculated output signal: (0) FALSE = a logic negation is applied; (1) TRUE =
no negation is applied.