PROGRAMMING
INSTRUCTIONS
SINUS PENTA
201/452
P295 MDO3: Function Applied to the Result of the 2 Tests
P295
Range
0
12
0: (A) OR (B)
1: (A) SET (B) RESET
2: (A) AND (B)
3: (A) XOR (B)
4: (A) NOR (B)
5: (A) NAND (B)
6: (A\) OR (B)
7: (A) OR (B\)
8: (A\) AND (B)
9: (A) AND (B\)
10: (A) RESET (B) SET RISING EDGE
11: (A) SET (B) RESET FALLING EDGE
12: (A) RESET (B) SET FALLING EDGE
Default
0
0: (A) OR (B)
Level
ADVANCED
Address
895
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value.
P295a MDO3: Selecting Variable C
P295a
Range
0
59
See Table 41
Default
0
D0: Disable
Level
ADVANCED
Address
646
Function
This parameter selects the digital signal used to calculate the value of
MDO3
digital output.
The digital signals that can be selected are given in Table 41.
P295b MDO3: Function Applied to the Result of f(A,B) C
P295b
Range
0
12
0: f(A,B) OR (C)
1: f(A,B) SET (C) RESET RISING EDGE
2: f(A,B) AND (C)
3: f(A,B) XOR (C)
4: f(A,B) NOR (C)
5: f(A,B) NAND (C)
6: f(A,B)\ OR (C)
7: f(A,B) OR (C\)
8: f(A,B)\ AND (C)
9: f(A,B) AND (C\)
10: f(A,B) RESET (C) SET RISING EDGE
11: f(A,B) SET (C) RESET FALLING EDGE
12: f(A,B) RESET (C) SET FALLING EDGE
Default
1
1: (A) SET (B) RESET
Level
ADVANCED
Address
647
Function
This parameter determines the logic function applied to the result of the two
tests allowing calculating the output value
.