SINUS PENTA
PROGRAMMING
INSTRUCTIONS
262/452
C041
M1
1041
C084
M2
1084
C127
M3
Fluxing ramp time
ENGINEERING
1127
See Table 74 and Table 78
C042
M1
1042
C085
M2
1085
C128
M3
Vout saturation percentage
ENGINEERING
1128
100%
C008 Rated Mains Voltage
C008
Range
0
8
0: [ 200
240 ] V
1: 2T Regen.
2: [ 380
480 ] V
3: [ 481
500 ] V
4: 4T Regen.
5: [ 500
600 ] V
6: 5T Regen.
7: [ 600
690 ] V
8: 6T Regen.
Default
2
2: [ 380
480 ] V
Level
BASIC
Address
1008
Function
This parameter defines the rated voltage of the mains powering the drive, thus
allowing obtaining voltage ranges to be used for the drive operation. The value
set in this parameter depends on the
Drive voltage class.
To supply the drive via a non-stabilized DC source, the corresponding AC
voltage range must be used (see Table 72). DO NOT USE xT Regen settings in
this case.
Table 72: Equivalence between AC mains range and DC range.
AC Mains
DC range
200
240 Vac 280
338 Vdc
380
480 Vac 530
678 Vdc
481
500 Vac 680
705 Vdc
500
600 Vac 705
810 Vdc
600
690 Vac 810
970 Vdc
NOTE
Select xT Regen
(where x relates to the voltage class of the drive)
if the drive is DC-
supplied through a regenerative Sinus Penta or a different drive used to stabilize
the DC bus to a higher level than the stabilization level obtained when rectifying
the 3-phase mains.
C009 N. of Configured Motors
C009
Range
1
3
1
3
Default
1
1
Level
ENGINEERING
Address
1009
Function
This parameter determines the number of motors to be configured. The active
motor is selected through digital inputs programmed with
C173
and
C174
(see
the DIGITAL INPUTS MENU).
The programming parameters of the Motor Control 2 Menu can be accessed only
if
C009
= 2 or 3; the programming parameters of the Motor Control 3 Menu can
be accessed only if
C009
=3.