SINUS PENTA
PROGRAMMING
INSTRUCTIONS
372/452
In Two PIDs mode:
if
C171a
=
0: Disabled
, the PID output is summed with the PID2 output;
if
C171a
is enabled, the logic state of the configured input determines which is the output of the PID regulator to be
used: 0
PID, 1
PID2.
In 2-zone mode:
if
C171a
is enabled, when the selected input is activated, the 2-zone mode (MIN or MAX) is disabled. In that case, the
PID regulator always operates on the error resulting from
C285
–
C288
and with parameters
P2xx
.
The PID regulator output may be used as:
an external output;
a speed/torque reference of the drive;
a speed/torque reference increase or, if the IFD control is used, the PID regulator input may be used for
correcting the output voltage.
If the PID regulator output is the speed reference of the drive, the selected speed/torque ramp is applied.
SERIAL LINK
The
Serial Link
source
is an input from the MODBUS link: the reference value shall be written by the user to the
following addresses:
Table 109: Reference sources from serial link.
MODBUS
Address
Input
User Level
Type of
Reference
Description
Unit of Measure
1418
I031
BASIC
PID Reference
PID reference value
Set in
P267
1420
I033
BASIC
PID Feedback
PID feedback value
Set in
P267
4 4.3.
List of Parameters C285 to C294
Table 110: List of parameters C285 to C294.
Paramete
r
FUNCTION
User Level
MODBUS
Address
Default
Values
C285
Selection of PID reference n. 1
ENGINEERIN
G
1285
2:AIN1
C286
Selection of PID reference n. 2
ENGINEERIN
G
1286
0:Disable
C287
Selection of PID reference n. 3
ENGINEERIN
G
1287
0:Disable
C288
Selection of PID feedback n. 1
ENGINEERIN
G
1288
3:AIN2/PTC
C289
Selection of PID feedback n. 2
ENGINEERIN
G
1289
0:Disable
C290
Selection of PID feedback n. 3
ENGINEERIN
G
1290
0:Disable
C291
PID operating mode
ENGINEERIN
G
1291
0:Disable
C291a
PID control mode
ENGINEERIN
G
1295
0:Standard
SUM
C291b
PID2 operating mode
ENGINEERIN
G
1296
1: Normal
C292
Selection of the variable for calculating the derivative
term
ENGINEERIN
G
1292
0:Measure
C293
Proportional Multiplier of derivative and integral terms
ENGINEERIN
G
1293
0:NO
C294
PID action
ENGINEERIN
G
1294
1:Reference