368/452
43.
MAINTENANCE
MENU
4 3.1.
Overview
The Maintenance menu allows setting partial counters for the drive Operation Time (OT) and Supply Time (ST). When
the preset time is reached, a warning message appears (
W48
OT Time over and
W49
ST Time over respectively).
4 3.2.
List of Parameters C275 to C278
Table 108: List of parameters C275 to C278.
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
C275
Operation time counter reset
ENGINEERING
1275
NO
C276
Operation time threshold
ENGINEERING
1276
0h
C277
Supply time counter reset
ENGINEERING
1277
NO
C278
Supply time threshold
ENGINEERING
1278
0h
C275 Operation time counter reset
C275
Range
0 ÷ 1
0: [NO]
1 [YES]
Default
0
NO
Level
ENGINEERING
Address
1275
Function
This parameter resets the partial counter for the drive operation time.
C276 Operation Time Threshold
C276
Range
0 ÷ 65000
0
650000h
Default
0
0h
Level
ENGINEERING
Address
1276
Function
This parameter sets the threshold for the operation time of the drive. When this time
is exceeded, Warning “
W48
OT Over
” appears. To reset the warning message, reset
the partial counter or set the counter threshold to zero.
C277 Supply Time Counter Reset
C277
Range
0 ÷ 1
0: [NO]
1 [YES]
Default
0
NO
Level
ENGINEERING
Address
1277
Function
This parameter resets the partial counter for the drive supply time.
C278 Supply Time Threshold
C278
Range
0 ÷ 65000
0
650000h
Default
0
0h
Level
ENGINEERING
Address
1278
Function
This parameter sets the threshold for the supply time of the drive. When this time is
exceeded, Warning “
W49
ST Over
” appears. To reset the warning message, reset the
partial counter or set the counter threshold to zero.