PROGRAMMING
INSTRUCTIONS
SINUS PENTA
85/452
P268 (P268a) Measure n.1 (n.2) on Root Page
P268 / P268a
Range
M000
M090
(see the MEASURES MENU)
Default
P268
M004
Motor Spd
P268a
M000
Speed Ref.
Level
ADVANCED
Address
Cannot be accessed via serial link.
Function
These two parameters allow selecting two measures to be displayed on the Root
Page.
P268y (P268z) Scaling of Measure n.1 (n.2) on Root page
P268y / P268z
Range
0
10000
0
100.00%
Default
10000
100.00%
Level
ADVANCED
Address
515 / 516
Function
These parameters allow scaling the read-out of the measures on the Root page
which have been selected with parameters
P268
and
P268a
.
P268b (P268c, P268d, P268e) Measure n.1 (n.2, n.3, n.4) on Keypad Page
P268b, P268c,
P268d, P268e
Range
M000
M090
(see the MEASURES MENU)
Default
P268b
M006
Mot.Freq.
P268c
M026
Motor Current
P268d
M004
Motor Spd
P268e
M000
Speed Ref.
Level
ADVANCED
Address
Cannot be accessed via serial link.
Function
These four parameters allow selecting four measures to be displayed on the
Keypad Page.
NOTE
Measure n. 4 is available in the measure Keypad page only. The reference to measure
n. 4 is available for the remaining Keypad pages.
P269 Disable LOC/REM FWD/REV Keys
P269
Range
0
3
0:[No No] - 3:[YES YES]
Default
0
0:[No No]
Level
ENGINEERING
Address
869
Function
This parameter allows disabling the
LOC/REM
and/or the
FWD/REV
key.
This is a bit-controlled parameter: bit 0 relates to
LOC/REM
, while bit 1 relates to
FWD/REV
. Set 0 to select [NO], set 1 to select [Yes].
P269
= 0
both keys are enabled.
P269
= 1
the
LOC/REM
key is disabled.
P269
= 2
the
FWD/REV
key is disabled.
P269
= 3