PROGRAMMING
INSTRUCTIONS
SINUS PENTA
207/452
P308 XMDO2: Signal Selection
P308
Range
0
59
See Table 41
Default
0
D0: Disable
Level
ENGINEERING
Address
908
Function
Selects the digital signal used to calculate the value of
XMDO2
digital output.
It selects an analog variable used to calculate the value of
XMDO2
digital input
if one of the “analog” operating modes is selected.
Digital signals and analog variables are detailed in Table 41.
P309 XMDO2: Output Logic Level
P309
Range
0–1
0: FALSE
1: TRUE
Default
1
1: TRUE
Level
ENGINEERING
Address
909
Function
XMDO2
digital output logic function to apply a logic reversal (negation) to the
calculated output signal: (0) FALSE = a logic negation is applied; (1) TRUE =
no negation is applied.
P310 XMDO3: Signal Selection
P310
Range
0
59
See Table 41
Default
0
D0: Disable
Level
ENGINEERING
Address
910
Function
Selects the digital signal used to calculate the value of
XMDO3
digital output.
It selects an analog variable used to calculate the value of
XMDO3
digital input
if one of the “analog” operating modes is selected.
Digital signals and analog variables are detailed in Table 41.
P311 XMDO3: Output Logic Level
P311
Range
0–1
0: FALSE
1: TRUE
Default
1
1: TRUE
Level
ENGINEERING
Address
911
Function
XMDO3
digital output logic function to apply a logic reversal (negation) to the
calculated output signal: (0) FALSE = a logic negation is applied; (1) TRUE =
no negation is applied.