PROGRAMMING
INSTRUCTIONS
SINUS PENTA
215/452
28.
VIRTUAL
DIGITAL
OUTPUTS
(MPL)
MENU
2 8.1.
Overview
The Virtual Digital Outputs menu includes the parameters allowing configuring the virtual digital outputs (MPL1..4) of
the Sinus Penta drive.
Virtual digital outputs are logic blocks (no hardware output is provided) allocating more complex logic functions to
outputs MDO1..4: MPL virtual outputs can be feedbacked at the input of a new block (hardware or virtual block), thus
allowing implementing more complex functionality.
NOTE
The Virtual Digital Outputs menu may be accessed only if the user level is ADVANCED or
ENGINEERING.
NOTE
XMDI auxiliary digital outputs (values from 13 to 20 in the parameters relating to the control
functions) can be set up only after setting XMDI/O in parameter
R023
.
28.1.1.
F
A CTORY
S
E TTING
MPL1 energizes when the ENABLE input is present; MPL2 energizes when a fan fault trips; MPL3 energizes when the
Fire Mode is activated; MPL4 is factory set as disabled.
28.1.2.
S
TRUCTURE OF THE
V
IRTUA L
D
IG ITA L
O
UTP UTS
A virtual digital output is composed of two logic blocks allowing data processing before actuating the actual digital
output. Block 2 depends on the settings in parameters
P357a
(
P366a
,
P375a,
P384a
).
Logic Block
set by
parameters
P351-P357
INPUT A
INPUT B
f(A,B)
P357a = 0
yes
Output= f(A,B)
NO
Logic block
set by P357b
that tests f(A,B)
and signal C
Output=
g[f(A,B),C]
P000658-b
Figure 38: Block diagram of the virtual digital outputs (MPL).
Operating modes set in MPL1 (2, 3, 4): P350, (P359, P368, P377)
The user can select one of the following operating modes: