SINUS PENTA
PROGRAMMING
INSTRUCTIONS
202/452
P296 MDO3: Output Logic Level
P296
Range
0–1
0: FALSE
1: TRUE
Default
0
0: FALSE
Level
ADVANCED
Address
896
Function
MDO3 digital output logic function to apply a logic reversal (negation) to the
calculated output signal: (0) FALSE = a logic negation is applied; (1) TRUE =
no negation is applied.
P297 MDO4: Digital Output Mode
P297
Range
0
8
0: DISABLE
1: DIGITAL
2: DOUBLE DIGITAL
3: ANALOG
4: DOUBLE ANALOG
5: DOUBLE FULL
6: BRAKE
7: ABS BRAKE
8: ABS LIFT
Default
1
1: DIGITAL
Level
ADVANCED
Address
897
Function
This parameter defines the operating mode of
digital output 4
. The different
operating modes are described at the beginning of this chapter.
P298 MDO4: Selecting Variable A
P298
Range
0
119
See Table 41.
Default
1
D1: Inverter Run Ok
Level
ADVANCED
Address
898
Function
This parameter selects the digital signal used to calculate the value of
MDO4
digital output.
It selects an analog variable used to calculate the value of
MDO4
digital input if
one of the “analog” operating modes is selected.
Digital signals and analog variables are detailed in Table 41.
P299 MDO4: Selecting Variable B
P299
Range
0
119
See Table 41
Default
1
D1: Inverter Run Ok
Level
ADVANCED
Address
899
Function
This parameter selects the second digital signal used to calculate the value of
MDO4
digital output.
It selects an analog variable used to calculate the value of
MDO4
digital input if
one of the “analog” operating modes is selected.
Digital signals and analog variables are detailed in Table 41.