PROGRAMMING
INSTRUCTIONS
SINUS PENTA
265/452
C012 (C055,C098) Speed Feedback from Encoder
C012 (Motor 1)
C055 (Motor 2)
C098 (Motor 3)
Range
0
1
0: No
1: Yes
Default
0
0
1
Level
BASIC
Address
1012, 1055, 1098
Control
VTC and FOC
Function
This parameter enables the encoder as a speed feedback.
It defines the encoder characteristics and whether Encoder A (MDI6 and MDI7 in
the terminal board) or Encoder B (with option board) is used as a speed feedback
(see the ENCODER/FREQUENCY INPUTS MENU).
C013 (C056, C099) Type of V/F Pattern
C013 (Motor 1)
C056 (Motor 2)
C099 (Motor 3)
Range
0
2
0: Constant Torque
1: Quadratic
2: Free Setting
Default
See Table 75 and Table 79
Level
BASIC
Address
1013, 1056, 1099
Control
IFD
Function
Allows selecting different types of V/f pattern.
If
C013 (C056,C099) = Constant torque
, voltage at zero frequency can be
selected (Preboost
C034
(
C077,C120
)).
If
C013 (C056,C099) = Quadratic
, you can select voltage at zero frequency
(preboost,
C034
(
C077,C120
)), max. voltage drop with respect to the theoretical
V/f pattern,
C032
(
C075 C118
), and the frequency allowing implementing max.
voltage drop,
C033
(
C076 C119
).
If
C013 (C056,C099) = Free Setting
, you can set voltage at zero frequency
(preboost,
C034
(
C077,C120
)); voltage increase to 20% of the rated frequency
(Boost0,
C035
(
C078,C121
)); and voltage increase to a programmed frequency
(Boost1,
C036
(
C079,C122
); frequency for Boost1,
C037
(
C080,C123
)).
C014 (C057, C100) Phase Rotation
C014 (Motor 1)
C057 (Motor 2)
C100 (Motor 3)
Range
0÷1
0: [No]; 1: [Yes]
Default
0
0: [No]
Level
ENGINEERING
Address
1014, 1057,1100
Function
Allows reversing the mechanical rotation of the connected motor.
DANGER!!!
When activating
C014 (C057, C100)
, the mechanical rotation of the connected motor
and its load is reversed accordingly.