C047 (C090, C133) Minimum Torque
C047 (Motor 1)
C090 (Motor 2)
C133 (Motor 3)
Range
–5000
5000 (*)
–500.0%
+500.0%
Default
0
0.0%
Level
ADVANCED
Address
1047, 1090, 1133
Control
VTC and FOC
Function
This parameter sets the min. limit of the torque demanded by the control being
used.
Torque is expressed as a percentage of the rated torque of the selected motor.
NOTE
If an external torque limit is set (
C147
in the
CONTROL METHOD MENU), the values
set in the parameters above represent the range of the source used for limitation; they
can be reduced by adjusting the external source; the torque ramp times set in the
RAMPS MENU will be applied to the preset limit torque reference (
P026–P027
).
C048 (C091, C134) Maximum Torque
C048 (Motor 1)
C091 (Motor 2)
C134 (Motor 3)
Range
–5000(*)
5000 (*)
–500.0%
+500.0%
Default
1200
120.0%
Level
BASIC (C048); ADVANCED (C091;C134)
Address
1048, 1091, 1134
Control
VTC and FOC
Function
This parameter sets the max. limit of the torque demanded by the control being
used.
Torque is expressed as a percentage of the rated torque of the selected motor.
NOTE
If an external torque limit is set (
C147
in the
CONTROL METHOD MENU), the values set in the
parameters above represent the range of the source used for limitation; the torque ramp times
set in the RAMPS MENU will be applied to the preset limit torque reference (
P026–P027
).
C049 (C092, C135) Ramp Time for Torque Limit
C049 (Motor 1)
C092 (Motor 2)
C135 (Motor 3)
Range
10
30000
10
30000ms
Default
50
50ms
Level
ADVANCED
Address
1049, 1092, 1135
Control
VTC and FOC
Function
This parameter sets the time taken by the torque limit of the selected motor to
go to zero from max. value.