PROGRAMMING
INSTRUCTIONS
SINUS PENTA
109/452
P057 Value of AIN1 Input Producing Max. Reference (X-axis)
P057
Range
–100
100, if
P055
= 0
–200
200, if
P055
= 1
+40
200, if
P055
= 2
0
100, if
P055
= 3
0
200, if
P055
= 4
–10.0 V
10.0 V, if
P055=
0:
10 V
–20.0 mA
20.0 mA, if
P055
= 1:
20 mA
+4.0mA
20.0 mA, if
P055
= 2: 4
20 mA
0.0 V
10.0V, if
P055
= 3: 0
10 V
0.0 mA
20.0 mA, if
P055
= 4: 0
20 mA
Default
200
+20.0mA
Level
ADVANCED
Address
657
Function
This parameter selects the value for AIN1 input signal for maximum reference, or
better the reference set in
C029xP057a
(Master mode) or in
C048xP057a
(Slave
mode). If motor 2 is active,
C072
and
C091
will be used instead of
C029
and
C048
;
if motor 3 is active, the values set in
C115
and
C134
will be used.
P057a Percentage of Speed_Max/Trq_Max Producing Max. Reference (Y-axis related to P057)
P057a
Range
0
1000
100.0%
Default
1000
100.0%
Level
ADVANCED
Address
678
Function
This parameter represents the min. speed percentage (or the min. torque percentage
for a torque reference) to be used for the minimum reference set with
P057.
P058 Offset over AIN1 Input
P058
Range
–2000
2000
–10.00 V
+10.00 V, if
P055 =
0 or 3
– 20.00 mA
+20.00 mA, if
P055
= 1,2,4
Default
0
0 V
Level
ADVANCED
Address
658
Function
This parameter selects the offset correction value of AIN1 analog signal that has
been measured.
The value set is added to the signal measured before saturation or conversion; its
unit of measure is the same as the one of the signal selected for AIN1 analog input.
P059 Filtering Time over AIN1 Input
P059
Range
0
+65000
0
+65000ms
Default
5
5 ms
Level
ADVANCED
Address
659
Function
This parameter selects the value of the filter time constant of the first command
applied to AIN1 input signal when the signal saturation and conversion is over.