SINUS PENTA
PROGRAMMING
INSTRUCTIONS
80/452
1 1.3.
Keypad Page and Local Mode
Keypad
+
0 . 0 H z
+
0 . 0 A
+
0 . 0 0 r p m
R e f
+ 1 5 0 0 . 0 0 r p m
Keypad Help
M 0 0 6 M o t . F r e q .
M 0 2 6
I ( R M S )
O u t
M 0 0 4 M o t o r
S p d
R e f
+ 1 5 0 0 . 0 0 r p m
To access the Keypad pages, press the
MENU
key
from the Root Page or press the
LOC/REM key
after selecting the
Local mode.
The measures displayed on the Keypad page can be set up through parameters
P268b
to
P268e
. From the Keypad
page, press the
SAVE/ENTER
key to display the Keypad Help page, describing the measures displayed on the Keypad
page. The Keypad Help page is displayed for a few seconds.
NOTE
If parameter
P264b
(Navigation mode via
MENU key)
is set to Operator, navigation is locked
once the Keypad Page is displayed. Hold down the
ESC
key for
a few seconds to resume
navigation.
The following Keypad Pages are available:
Measures only
four lines displaying measures only
Speed
line 4 shows the speed reference, that can be changed with the
▲
and
▼
keys.
Torque
line 4 shows the torque reference, that can be changed with the
▲
and
▼
keys.
Limit Torque
line 4 shows the limit torque reference, that can be changed with the
▲
and
▼
keys.
PID
line 4 shows the PID reference, that can be changed with the
▲
and
▼
keys.
If the Local Mode is NOT selected, pressing the MENU key allows viewing only the pages containing the references
sent via keypad (see the CONTROL METHOD MENU and the PID CONFIGURATION MENU).
LOCAL MODE
In
LOCAL
mode (the L-CMD and L-REF LEDs come on when the Local mode is active), only the commands and
references sent via keypad are enabled, while any other control source or reference source is disabled (see the
CONTROL METHOD MENU, the DIGITAL INPUTS MENU and the INPUTS FOR REFERENCES MENU). The keypad
page displayed when the
LOC/REM
key is pressed depends on the setting of parameter
P266
(Type of Keypad Page in
Local Mode):
P266 = Measures Only
Page containing 4 preset measures; no reference can be changed.
P266 = Ref.Activated
Line 4 in the Keypad Page enables changing the drive reference: the speed reference if a
speed control is activated (“Ref” displayed), the torque reference if a torque control is activated (“TRef” displayed). If
the drive reference is the PID output (
C294
PID Action = 1:[Reference]), the PID reference is given (“PRef” displayed).
Use the
▲
and
▼
keys to change the reference displayed in line 4 on the Keypad Page.
P266 = Ref.AcSpd
To be used only when the drive reference depends on the PID output when a speed
control is used (
C294
PID Action = 1:[Reference]). When the
LOC/REM
key is pressed for the first time, “PRef” is
displayed in line 4 and the PID reference may be adjusted; when the
LOC/REM
key is pressed twice, the PID is
disabled and the speed reference can be changed (“Ref” displayed).
Use the
▲
and
▼
keys to change the reference shown in line 4 on the Keypad Page.
SAVE/
ENTER