The fault-related current, voltage, frequency, angle values, shot pointer and the active
setting group number are taken from the moment of the operate event, or from the
beginning of the fault if only a pickup event occurs during the fault. The maximum current
value collects the maximum fault currents during the fault. In case frequency cannot be
measured, nominal frequency is used for frequency and zero for Frequency gradient and
validity is set accordingly.
Measuring mode for phase current and residual current values can be selected with the
Measurement mode
setting parameter.
3.7.2
Settings
Table 33:
FR Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation Disable / Enable
Trig mode
0=Trip or Pickup
1=Trip only
2=Pickup only
0=Trip or Pickup
Triggering mode
Measurement mode
1=RMS
2=DFT
3=Peak-to-Peak
2=DFT
Selects used measurement mode
Section 3
1MRS240050-IB C
Basic functions
68
REF615R
Technical Manual