no reboot is necessary, the time synchronization starts immediately after the IRIG-B sync
source is selected and the IRIG-B signal source is connected.
ABB has tested the IRIG-B with the following clock masters.
•
Tekron TTM01 GPS clock with IRIG-B output
•
Meinberg TCG511 controlled by GPS167
•
Datum ET6000L
•
Arbiter Systems 1088B
IRIG-B time synchronization requires a COM card with an IRIG-B input.
Available only with some models.
3.6
Parameter setting groups
3.6.1
Function block
GUID-76F71815-D82D-4D81-BCFE-28AF2D56391A V1 EN
Figure 20:
Function block
3.6.2
Functionality
The protection relay supports six setting groups. Each setting group contains parameters
categorized as group settings inside application functions. The customer can change the
active setting group at run time.
The active setting group can be changed by a parameter or via binary inputs depending on
the mode selected with the
Configuration/Setting Group/SG operation mode
setting.
The default value of all inputs is FALSE, which makes it possible to use only the required
number of inputs and leave the rest disconnected. The setting group selection is not
dependent on the
SG_x_ACT
outputs.
1MRS240050-IB C
Section 3
Basic functions
REF615R
65
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...