Table 364:
52 Output signals
Name
Type
Description
SELECTED
BOOLEAN
Object selected
EXE_OP
BOOLEAN
Executes the command for open direction
EXE_CL
BOOLEAN
Executes the command for close direction
OPENPOS
BOOLEAN
Apparatus open position
CLOSEPOS
BOOLEAN
Apparatus closed position
OKPOS
BOOLEAN
Apparatus position is ok
OPEN_ENAD
BOOLEAN
Opening is enabled based on the input status
CLOSE_ENAD
BOOLEAN
Closing is enabled based on the input status
9.1.7
Settings
Table 365:
52 Non group settings
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=enable
5=disable
1=enable
Operation mode disable / disable
Select timeout
10000...300000
ms
10000
60000
Select timeout in ms
Pulse length
10...60000
ms
1
100
Open and close pulse length
Operation counter
0...10000
0
Breaker operation cycles
Control model
0=status-only
1=direct-with-
normal-security
4=sbo-with-
enhanced-security
4=sbo-with-
enhanced-security
Select control model
Adaptive pulse
0=False
1=True
1=True
Stop in right position
Event delay
0...10000
ms
1
100
Event delay of the intermediate position
Operation timeout
10...60000
ms
500
Timeout for negative termination
9.1.8
Monitored data
Table 366:
52 Monitored data
Name
Type
Values (Range)
Unit
Description
POSITION
Dbpos
0=intermediate
1=open
2=closed
3=faulty
Apparatus position indication
Section 9
1MRS240050-IB C
Control functions
456
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...