Figure 197:
Functional module diagram
Negative phase-sequence criterion
A fuse failure based on the negative-sequence criterion is detected if the measured
negative-sequence voltage exceeds the set
Neg Seq voltage Lev
value and the measured
negative-sequence current is below the set
Neg Seq current Lev
value. The detected fuse
failure is reported to the decision logic module.
Voltage check
The phase voltage magnitude is checked when deciding whether the fuse failure is a three,
two or a single-phase fault.
The module makes a phase-specific comparison between each voltage input and the
Seal
in voltage
setting. If the input voltage is lower than the setting, the corresponding phase
is reported to the decision logic module.
Current and voltage delta criterion
The delta function can be activated by setting the
Change rate enable
parameter to "True".
Once the function is activated, it operates in parallel with the negative sequence-based
algorithm. The current and voltage are continuously measured in all three phases to
calculate:
Section 6
1MRS240050-IB C
Supervision functions
372
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...