VN
I2
BLOCK
RELEASE
Blocking
logic
IG
IN
RCA_CTL
t
Timer
VG
V2
Directional
detector
Low level
blocking
DIRECTION
GUID-C8755615-9FDA-41DD-9245-DBA7EC6A77CB-ANSI V1 EN
Figure 136:
Functional module diagram
Directional detector
When "Neg. seq. volt." selection is made using
Pol signal Sel
, the Directional detector
module compares the angle of the negative-sequence current (I2) to the negative-sequence
voltage (-V2). Using the negative-sequence voltage angle as the reference, the negative-
sequence current angle is compared to the
Characteristic angle
setting. If the angle
difference is within the operating sector selected by
Direction mode
setting, the Enable
signal is sent to Timer.
The value of
Characteristic angle
should be chosen in such way that all
the faults in the operating direction are seen in the operating zone and all
the faults in the opposite direction are seen in the backward zone.
The operating sector is defined by the settings
Max forward angle
,
Max reverse angle
,
Min
forward angle
and
Min reverse angle
. The options that can be selected for
Directional
mode
settings are “Forward” and “Reverse”.
Characteristic angle
is also known as Relay Characteristic Angle RCA, Relay Base Angle
or Maximum Torque Line.
Section 4
1MRS240050-IB C
Protection functions
288
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...