level
parameters can be set to get notification about memory consumption reaching a
certain level. Therefore the data can be uploaded before the oldest data gets overwritten.
To re-enable notifications via
Mem. warning level
and
Mem. alarm level
parameters, the
load profile record should be cleared after uploading. State change of
Mem. warning level
or
Mem. alarm level
parameters generates an event.
The IP number of the protection relay and the content of the
Bay name
setting are both included in the COMTRADE configuration file for
identification purposes.
3.15.3
Signals
Table 64:
LoadProf Output signals
Name
Type
Description
MEM_WARN
BOOLEAN
Recording memory warning status
MEM_ALARM
BOOLEAN
Recording memory alarm status
Section 3
1MRS240050-IB C
Basic functions
108
REF615R
Technical Manual