Table 449:
2-wire EIA-485 jumper connectors
Group
Jumper connection
Description
Notes
X4
1-2
A+ bias enabled
COM2
2-wire connection
2-3
A+ bias disabled
X5
1-2
B- bias enabled
2-3
B- bias disabled
X6
1-2
Bus termination enabled
2-3
Bus termination disabled
X7
1-2
B- bias enabled
COM1
2-wire connection
2-3
B- bias disabled
X8
1-2
A+ bias enabled
2-3
A+ bias disabled
X9
1-2
Bus termination enabled
2-3
Bus termination disabled
The bus is to be biased at one end to ensure fail-safe operation, which can be done using
the pull-up and pull-down resistors on the communication module. In 4-wire connection
the pull-up and pull-down resistors are selected by setting jumpers X4, X5, X7 and X8 to
enabled position. The bus termination is selected by setting jumpers X6 and X9 to enabled
position.
The jumpers have been set to no termination and no biasing as default.
Table 450:
4-wire EIA-485 jumper connectors for COM2
Group
Jumper connection
Description
Notes
X4
1-2
A+ bias enabled
COM2
4-wire TX channel
2-3
A+ bias disabled
1)
X5
1-2
B- bias enabled
2-3
B- bias disabled
1)
X6
1-2
Bus termination enabled
2-3
Bus termination disabled
1)
X7
1-2
B- bias enabled
COM2
4-wire RX channel
2-3
B- bias disabled
1)
X8
1-2
A+ bias enabled
2-3
A+ bias disabled
1)
X9
1-2
Bus termination enabled
2-3
Bus termination disabled
1)
1) Default setting
1MRS240050-IB C
Section 14
Protection relay's physical connections
REF615R
633
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...