Str 2 delay shot 1
•
Str 2 delay shot 2
•
Str 2 delay shot 3
•
Str 2 delay shot 4
Time delay settings for the
DEL_INIT_3
signal
•
Str 3 delay shot 1
•
Str 3 delay shot 2
•
Str 3 delay shot 3
•
Str 3 delay shot 4
Time delay settings for the
DEL_INIT_4
signal
•
Str 4 delay shot 1
•
Str 4 delay shot 2
•
Str 4 delay shot 3
•
Str 4 delay shot 4
Normally, only two or three reclosing attempts are made. The third and fourth attempts are
used to provide the so-called fast final trip to lockout.
GUID-36912067-F77E-457B-87D8-637CE0FA73A6 V1 EN
Figure 239:
Autoreclosing configuration example
Delayed
DEL_INIT_2...4
signals are used only when the autoreclosing shot is
initiated with the pickup signal of a protection stage. After a pickup delay, the AR function
opens the circuit breaker and an autoreclosing shot is initiated. When the shot is initiated
with the trip signal of the protection, the protection function trips the circuit breaker and
simultaneously initiates the autoreclosing shot.
1MRS240050-IB C
Section 9
Control functions
REF615R
463
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...