In the DT mode, the function trips after a predefined trip time and resets when the fault
current disappears. The IDMT mode provides current-dependent timer characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
timers or the function itself, if desired.
4.1.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
The operation of 51P/50P can be described by using a module diagram. All the modules
in the diagram are explained in the next sections.
A070552-ANSI V1 EN
Figure 54:
Functional module diagram
Level detector
The measured phase currents are compared phasewise to the set
Pickup value
. If the
measured value exceeds the set
Pickup value
, the level detector reports the exceeding of
the value to the phase selection logic. If the
ENA_MULT
input is active, the
Pickup value
setting is multiplied by the
Pickup value Mult
setting.
Do not set the multiplier setting
Pickup value Mult
higher than necessary.
If the value is too high, the function may not trip at all during an inrush
followed by a fault, no matter how severe the fault is.
The pickup value multiplication is normally done when the inrush detection function
(INR) is connected to the
ENA_MULT
input.
Section 4
1MRS240050-IB C
Protection functions
114
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...