A071274-ANSI V1 EN
Figure 256:
Three shots with three initiation lines
If the sequence is initiated from the
INIT_1
line, that is, the overcurrent protection high
stage, the sequence is one shot long. If the sequence is initiated from the
INIT_2
or
INIT_3
lines, the sequence is two shots long.
Table 370:
Settings for configuration example 2
Setting name
Setting value
Shot number CBB1
1
Init signals CBB1
1 (line 1)
First reclose time
0.0s (an example)
Shot number CBB2
1
Init signals CBB2
6 (lines 2 and 3 = 2+4 = 6)
Second reclose time
0.2s (an example)
Shot number CBB3
2
Init signals CBB3
6 (lines 2 and 3 = 2+4 = 6)
Third reclose time
10.0s
9.2.6.4
Delayed initiation lines
The autoreclose function consists of six individual autoreclose initiation lines
INIT_1...INIT 6
and three delayed initiation lines:
•
DEL_INIT_2
•
DEL_INIT_3
•
DEL_INIT_4
DEL_INIT_2
and
INIT_2
are connected together with an OR-gate, as are inputs 3 and
4. Inputs 1, 5 and 6 do not have any delayed input. From the autoreclosing point of view,
it does not matter whether
INIT_x
or
DEL_INIT_x
line is used for shot initiation or
blocking.
Section 9
1MRS240050-IB C
Control functions
488
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...