relays are also used to have a selective protection scheme, for example in case of parallel
distribution lines or power transformers fed by the same single source.In ring connected
supply feeders between substations or feeders with two feeding sources, 67/51P and
67/50P is also used.
Parallel lines or transformers
When the lines are connected in parallel and if a fault occurs in one of the lines, it is
practical to have 67/51P and 67/50P to detect the direction of the fault. Otherwise, there
is a risk that the fault situation in one part of the feeding system can de-energize the whole
system connected to the LV side.
GUID-E92DF9EA-D7AD-4866-B426-08533D5E2973-ANSI V1 EN
Figure 75:
Overcurrent protection of parallel lines using directional protection relays
67/51P and 67/50P can be used for parallel operating transformer applications. In these
applications, there is a possibility that the fault current can also be fed from the LV-side
up to the HV-side. Therefore, the transformer is also equipped with directional
overcurrent protection.
Section 4
1MRS240050-IB C
Protection functions
152
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...