11.5
Generic control points CNTRL
11.5.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/
IEEEidentification
Generic control points
SPCGGIO
SPC
CNTRL
11.5.2
Function block
GUID-C2A6026C-1E8D-4382-9675-2C63E413998B V1 EN
Figure 285:
Function block
11.5.3
Functionality
The generic control points function CNTRL can be used in combination with other
function blocks such as FKEYGGIO. SPC offers the capability to activate its outputs
through a local or remote control. The local control is provided through the buttons in the
front panel and the remote control is provided through communications. CNTRL has two
modes of operation. In the "Toggle" mode, the block toggles the output signal for every
input pulse received. In the "Pulsed" mode, the block generates an output pulse of a preset
duration.
11.5.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
Section 11
1MRS240050-IB C
Other functions
544
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...