9.2.6.1
Shot initiation
A070869 V1 EN
Figure 249:
Example of an autoreclosing program with a reclose scheme matrix
In the AR function, each shot can be programmed to locate anywhere in the reclose
scheme matrix. The shots are like building blocks used to design the reclose program. The
building blocks are called CBBs. All blocks are alike and have settings which give the
attempt number (columns in the matrix), the initiation or blocking signals (rows in the
matrix) and the reclose time of the shot.
The settings related to CBB configuration are:
•
First...Seventh reclose time
•
Init signals CBB1…CBB7
•
Blk signals CBB1…CBB7
•
Shot number CBB1…CBB7
The reclose time defines the open and dead times, that is, the time between the
OPEN_CB
and the
CLOSE_CB
commands. The
Init signals CBBx
setting defines the initiation
Section 9
1MRS240050-IB C
Control functions
478
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...