is activated, but only for the reclaim time after energizing the power line and only when
the circuit breaker is closed manually and not by the AR function.
SOTF disables any initiation of an autoreclosing shot. The energizing of the power line is
detected from the
CB_POS
information.
SOTF is activated when the AR function is enabled or when the AR function is started and
the SOTF should remain active for the reclaim time.
When SOTF is detected, the parameter
SOTF
is active.
If the
Manual close mode
setting is set to FALSE and the circuit breaker
has been manually closed during an autoreclosing shot, the AR unit goes
to an immediate lockout.
If the
Manual close mode
setting is set to TRUE and the circuit breaker has
been manually closed during an autoreclosing shot (the
INPRO
is active),
the shot is considered as completed.
When SOTF starts, reclaim time is restarted, provided that it is running.
The frequent-operation counter is intended for blocking the autoreclosing function in
cases where the fault causes repetitive autoreclosing sequences during a short period of
time. For instance, if a tree causes a short circuit and, as a result, there are autoreclosing
shots within a few minutes interval during a stormy night. These types of faults can easily
damage the circuit breaker if the AR function is not locked by a frequent-operation
counter.
The frequent-operation counter has three settings:
•
Frq Op counter limit
•
Frq Op counter time
•
Frq Op recovery time
The
Frq Op counter limit
setting defines the number of reclose attempts that are allowed
during the time defined with the
Frq Op counter time
setting. If the set value is reached
within a pre-defined period defined with the
Frq Op counter time
setting, the AR function
goes to lockout when a new shot begins, provided that the counter is still above the set
1MRS240050-IB C
Section 9
Control functions
REF615R
475
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...