A070875-ANSI V1 EN
Figure 248:
Configuration example of using the
PROT_CRD
output for protection
blocking
If the
Protection crd limit
setting has the value "1", the instantaneous three-phase
overcurrent protection function 50P-3 is disabled or blocked after the first shot.
9.2.4.7
Circuit breaker controller
Circuit breaker controller contains two features: SOTF and frequent-operation counter.
SOTF protects the AR function in permanent faults.
The circuit breaker position information is controlled with the
CB closed Pos status
setting. The setting value "TRUE” means that when the circuit breaker is closed, the
CB_POS
input is TRUE. When the setting value is “FALSE”, the
CB_POS
input is
FALSE, provided that the circuit breaker is closed. The reclose command pulse time can
be controlled with the
Close pulse time
setting: the
CLOSE_CB
output is active for the
time set with the
Close pulse time
setting. The
CLOSE_CB
output is deactivated also when
the circuit breaker is detected to be closed, that is, when the
CB_POS
input changes from
open state to closed state. The
Wait close time
setting defines the time after the
CLOSE_CB
command activation, during which the circuit breaker should be closed. If the
closing of circuit breaker does not happen during this time, the autoreclosing function is
driven to lockout or, if allowed, an auto-initiation is activated.
The main motivation for autoreclosing to begin with is the assumption that the fault is
temporary by nature, and that a momentary de-energizing of the power line and an
automatic reclosing restores the power supply. However, when the power line is manually
energized and an immediate protection trip is detected, it is very likely that the fault is of
a permanent type. A permanent fault is, for example, energizing a power line into a
forgotten grounding after a maintenance work along the power line. In such cases, SOTF
Section 9
1MRS240050-IB C
Control functions
474
REF615R
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...