11.7.3
Functionality
The local generic control points function LCNTRL is dedicated only for local controlling,
that is, LCNTRL cannot be controlled remotely. The local control is done through the
buttons in the front panel.
11.7.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The corresponding
parameter values are “Enable” and “Disable”.
LCNTRL has the
Operation mode
,
Pulse length
and
Description
settings available to
control all 16 outputs. By default, the
Operation mode
setting is set to "Off". This disables
the controllable signal output. LCNTRL also has a general setting
Loc Rem restriction
,
which enables or disables the local or remote state functionality.
When the
Operation mode
is set to "Toggle", the corresponding output toggles between
"True" and "False" for every input pulse received. The state of the output is stored in a
nonvolatile memory and restored if the protection relay is restarted.
When the
Operation mode
is set to "Pulsed", the corresponding output can be used to
produce the predefined length of pulses. Once activated, the output remains active for the
duration of the set pulse length. When activated, the additional activation command does
not extend the length of pulse. Thus, the pulse needs to be ended before the new activation
can occur.
The
Description
setting can be used for storing signal names for each output.
Each control point or LCNTRL can only be accessed through the LHMI control. LCNTRL
follows the local or remote (L/R) state if the
Loc Rem restriction
setting is "true". If the
Loc Rem restriction
setting is "false", local or remote (L/R) state is ignored, that is, all
controls are allowed regardless of the local or remote state.
The
BLOCK
input can be used for blocking the output functionality. The
BLOCK
input
operation depends on the
Operation mode
setting. If the
Operation mode
setting is set to
"Toggle", the output state cannot be changed when the input
BLOCK
is TRUE. If the
Operation mode
setting is set to "Pulsed", the activation of the
BLOCK
input resets the
output to the FALSE state.
From the remote communication point of view, SPCGGIO toggled
operation mode is always working as persistent mode. The output
O#
follows the value written to the input
IN#
.
1MRS240050-IB C
Section 11
Other functions
REF615R
555
Technical Manual
Summary of Contents for RELION REF615R
Page 1: ... RELION PROTECTION AND CONTROL REF615R Technical Manual ...
Page 2: ......
Page 27: ...Section 18 Glossary 653 Table of contents REF615R 21 Technical Manual ...
Page 28: ...22 ...
Page 36: ...30 ...
Page 46: ...40 ...
Page 115: ...3 15 4 Settings 1MRS240050 IB C Section 3 Basic functions REF615R 109 Technical Manual ...
Page 118: ...112 ...
Page 318: ...312 ...
Page 388: ...382 ...
Page 456: ...450 ...
Page 520: ...514 ...
Page 652: ...646 ...
Page 656: ...650 ...
Page 658: ...652 ...
Page 663: ...657 ...